Air Filters

Met - Pleat Filter

The Met Pleat filter series comprises of pleated cassette type filters. They are typically used in the Air supply/Air handling units such as Automotive Paint shops, Offices, Shopping malls, Airports, Pharmaceuticals, Biotech labs, Semiconductor & other industries. These products can be engineered to deliver specific value to our customers.

You could choose from the following options:

Media: Synthetic-self-supporting/supported, FPCP, washable & disposable

Frame: Galvanised iron, aluminium, plastic and carton

Construction: Box/flange type

Specification Value
MERV 5 - 15
EN779 G3 + F9
Eurovent 4/5 EU3 - EU5

UNSUPPORTED DISPOSABLE MEDIA

TYPICAL FILTER DATA FOR STANDARD FILTER SIZE AS PER DIN EN 779/ASHRAE

Product Code Media Type Grade Dimension Rated Air Flow (CMH) DP Initial (Pa) DP Final (Pa)
G3 Synthetic Media G3 610x610x50mm 3400 35 250
G3 G3 610x305x50mm 1700 35 250
G4 Synthetic Media G4 610x610x50mm 3400 40 250
G4 G4 610x305x50mm 1700 40 250
F5 Synthetic Media F5 610x610x300mm 3400 70 450
F5 Synthetic Media F5 610x305x300mm 1700 70 450
F7 Synthetic Media F7 610x610x300mm 3400 90 450
F7 Synthetic Media F7 610x305x300mm 1700 90 450
F9 Synthetic Media F9 610x610x300mm 3400 130 450
F9 Synthetic Media F9 610x305x300mm 1700 130 450
F5 Glass Fiber F5 610x610x300mm 3400 80 450
F5 Glass Fiber F5 610x305x300mm 1700 80 450
F7 Glass Fiber F7 610x610x300mm 3400 100 450
F7 Glass Fiber F7 610x305x300mm 1700 100 450
F9 Glass Fiber F9 610x610x300mm 3400 150 450
F9 Glass Fiber F9 610x305x300mm 1700 150 450

Dimensions other than the ones mentioned are also available on request in both box & flange type.

The data provided is indicative only. For actual specification, the user is requested to call our technical support to ascertain the correct values. Also, the data of various types and brands are comparable only if they have been tested under the same norm.

Dust holding capacity is measured according to DIN EN 779/ASHRAE until the rated final pressure drop is achieved. In case higher final pressures at economical operations are feasible, dust holding capacity increases correspondingly.

PRODUCT SELECTION MATRIX /APPLICATION GUIDE

Market Application Primary Filter Secondary Filter
Automative OEMs & Auto Ancillary Unit In Air Supply Units for Paint Shops G3-G4
Clean Rooms Pharmaceuticals, Biotech labs, Semiconductor, Food & Beverages, Hospital, Research labs G3-G4 F5, F7
Others Gas Turbines, ASU G3-G4
Textiles, Chemicals & Fertilisers As Fresh Air intake for Process area G3-G4 F5, F7

The product selection matrix is to highlight the potential application areas and for starting point reference only. However, for specific application requirement, users are requested to consult our technical product specialists.

Deep Pleat HEPA Filters

Deep Pleat HEPA Filters

Met Deep Pleat HEPA filters are made from water-resistant, fire-retardant, microfine glass fibre media. These filters are designed to accommodate regular air flow volumes. A 610 mm x 610 mm x 300 mm filter can handle air flow volumes up to 1000 cfm or 1700 cmh. This category of filters is mostly used in healthcare industries, pharmaceuticals, biotech labs, R&D labs, food & beverage companies, electronics, the semiconductor industry, and other dust-critical process industries.

You could choose from the following options:

Frame: Aluminium, Anodised/Non-anodised MS powder coated, SS & plastic

Construction: Box/flange type

MERV 3-14
EN1822 G2+F9
Eurovent A/S EU3-EU9

TECHNICAL DATA SHEET: (TESTING AS PER EN 1822 & ISO 14644)

Product Code Grade Dimension Rated Air Flow (CMH) Dp Initial (Pa) Dp Final (Pa)
H13 H13 610x610x150mm 1700 280 750
H13 H13 610x305x150mm 850
H13 H13 610x610x300mm 3400
H13 H13 610x305x300mm 1700
H14 H14 610x610x150mm 1700 320 750
H14 H14 610x305x150mm 850
H14 H14 610x610x300mm 3400
H14 H14 610x305x300mm 1700

The data provided is indicative only. For actual specification, the user is requested to call our technical specialists to ascertain the correct values. Also the data of various types and brands are comparable only if they have been tested under the same norm. Dust holding capacity is measured according to DIN EN 779/ASHRAE until the rated final pressure drop is achieved. In case higher final pressures at economical operations are feasible, dust holding capacity increases correspondingly.

PRODUCT SELECTION MATRIX / APPLICATION GUIDE

Application Terminal Filter
Cleanrooms
Pharmaceuticals H13
Electronics & Semiconductor H13
Hospitals H13, H14
Biotech labs H13, H14
Research labs H13, H14
Others
Nuclear power plants H13, H14
Textiles (air compressor plants) H13, H14

The product selection matrix is to highlight the potential application areas and for starting point reference only. However, for specific application requirement, users are requested to consult our product specialists.

Super Deep Flat HEPA filters

Super Deep Pleat HEPA Filters

Met Super Deep Flat HEPA filters are made from water resistant, fire retardant moline glass fibre media. These Filter are designed to accommodate high air flow volumes. A 610 mm x 610 mm x 300 mm filter can accommodate upto 2000 cfm or 3.400 cmh. This category of filters is mostly used in healthcare industries, Pharmaceuticals, Biotech labs R&D labs, Food & Beverage companies, Electronics, Manufacturing and other dust critical process industries.

You could choose from the following options:

Frame: Aluminium, anodised/without anodised MS powder coated and SS

Construction: Box/flange type/Header

Specification Value
MERV 16-20
EN 1822 H10-H14
Eurovent 4/5 EU10 - EU14
IEST RP CC 001.3 A, B, C, D

TECHNICAL DATA SHEET: (TESTING AS PER EN 1822 & ISO 14644)

Product Code Grade Dimension Rated Air Flow (CMH) Dp Initial (pa) Dp Final (pa)
H13 H13 610x610x150mm 1700 280 750
H13 H13 610x305x150mm 850
H13 H13 610x610x300mm 3400
H13 H13 610x305x300mm 1700
H14 H14 610x610x150mm 1700 320 750
H14 H14 610x305x150mm 850
H14 H14 610x610x300mm 3400
H14 H14 610x305x300mm 1700

The data provided is indicative only. For actual specification, the user is requested to call our technical specialists to ascertain the correct values. Also the data of various types and brands are comparable only if they have been tested under the same norm. Dust holding capacity is measured according to DIN EN 779/ASHRAE until the rated final pressure drop is achieved. In case higher final pressures at economical operations are feasible, dust holding capacity increases correspondingly.

PRODUCT SELECTION MATRIX / APPLICATION GUIDE

Application Terminal Filter
Cleanrooms
Pharmaceuticals H13
Electronics & Semiconductor H13
Hospitals H13, H14
Biotech labs H13, H14
Research labs H13, H14
Others
Nuclear power plants H13, H14
Textiles (air compressor plants) H13, H14

The product selection matrix is to highlight the potential application areas and for starting point reference only. However, for specific application requirement, users are requested to consult our product specialists.

 High Temp D Pleat Hepa Filter 

High Temp D Pleat Hepa Filter

Our’s MET HT-Set and Super are examples of a new high temperature HEPA filtration technology. Specifically designed for use in dehydrogenation ovens, tunnels for sterilization purposes and in FBD tunnels, High temperature HEPA filters are also used in aseptic clean side operation (supply air) of manufacturing and in pharmaceutical regulatory agencies processes to remove pyrogens to assure that they are suitable for their intended use.

Standard Grade
EN 1822 H13 - H14
Eurovent 4/5 EU13 - EU14
IEST RP CC 001.3 A, B, C, D

TECHNICAL DATA SHEET: (TESTING AS PER EN 1822)

Product Code Grade Dimension Rated Air Flow (CMH) Dp initial (pa) Dp Final (pa)
H13 H13 610X610X150mm 850 250 750
H13 H13 610x305x150mm 425 250 750
H13 H13 610x610x300mm 1700 250 750
H13 H13 610x305x300mm 850 250 750
H14 H14 610X610X150mm 850 280 750
H14 H14 610x305x150mm 425 280 750
H14 H14 610x610x300mm 1700 280 750
H14 H14 610x305x300mm 850 280 750
  • Temperature stability upto 350 C
  • Dimension other than the ones mentioned are also available on request

TECHNICAL DATA SHEET: (TESTING AS PER EN 1822)

Product Code Grade Dimension Rated Air Flow (CMH) Dp initial (pa) Dp Final (pa)
H13 H13 610X610X150mm 1700 280 750
H13 H13 610x305x150mm 850 280 750
H13 H13 610x610x300mm 3400 280 750
H13 H13 610x305x300mm 1700 280 750
H14 H14 610X610X150mm 1700 320 750
H14 H14 610x305x150mm 850 320 750
H14 H14 610x610x300mm 3400 320 750
H14 H14 610x305x300mm 1700 320 750

The data provided is indicative only. For actual specification, the user is requested to call our technical specialists to ascertain the correct values. Also, the data of various types and brands are comparable only if they have been tested under the same norm. Dust holding capacity is measured according to DIN EN 779/ASHRAE until the rated final pressure drop is achieved. In case higher final pressures at economical operations are feasible, dust holding capacity increases correspondingly.

The data provided is indicative only. For actual specification, the user is requested to call our technical specialists to ascertain the correct values. Also, the data of various types and brands are comparable only if they have been tested under the same norm. Dust holding capacity is measured according to DIN EN 779/ASHRAE until the rated final pressure drop is achieved. In case higher final pressures at economical operations are feasible, dust holding capacity increases correspondingly.

Met – Pocket Filter

Met – Pocket Filter

The Met Pocket filter series is an excellent choice for secondary & fine filter requirement, it is generally used in

Automotive paint booths, Health Care facilities,
Commercial buildings and other industrial filtration requirements. Available in both synthetic and glass fibre media, these filters can be designed with varying number of pockets to suit different air flow requirements.

Pocket filters lend flexibility for upgrading of the air quality to meet the needs of the manufacturer. These are also cost effective and highly efficient since there is very little metal support and what is discarded is mostly the choked media which in any case needs to be discarded.

You could choose from the following options:
Media: Synthetic (High loft, standard loft with/without aerodynamic spacers) Glass fibre media
Frame: Galvanised iron, aluminium, plastic & powder coated MS
Edge Sealing: Ultrasonically welded, stitched
Construction: Box /Flange

MERV EN 779 Eurovent 4/5
5-15 G3- F9 EU3- EU9

TYPICAL FILTER DATA FOR STANDARD FILTER SIZE AS PER DIN EN 779/ASHRAE

Product Code Media Type Grade Dimension No. Pocket Rated Air Flow (CMH) Dp Initial (Pa) Dp Final (Pa)
G3 Synthetic Media G4 592x592x360 6 3400 60 250
G3 Synthetic Media G4 592x292x360 6 1700 60 250
G4 Synthetic Media G4 592x592x600 6 3400 40 250
G4 Synthetic Media G4 592x292x600 6 1700 40 250
F5 Synthetic Media F5 592x592x600 8 3400 70 450
F5 Synthetic Media F5 592x292x600 8 1700 70 450
F7 Synthetic Media F7 592x592x600 10 3400 90 450
F7 Synthetic Media F7 592x292x600 10 1700 90 450
F9 Synthetic Media F9 592x592x600 10 3400 120 450
F9 Synthetic Media F9 592x292x600 10 1700 120 450

The data provided is indicative only. For actual specification, the user is requested to call our technical specialists to ascertain the correct values. Also the data of various types and brands are comparable only if they have been tested under the same norm.

Dust holding capacity is measured according to DIN EN 779/ASHRAE until the rated final pressure drop is achieved. In case higher final pressures at economical operations are feasible, dust holding capacity increases correspondingly.

PRODUCT SELECTION MATRIX / APPLICATION GUIDE

Markets Application Primary Filter Secondary Filter
Automotive OEMs & Auto Ancillary Units In ASUs for Paint shops G4, F5, F6 F5, F6, F7, F8
HVAC, Airports shopping malls & Hotels In ASUs for fresh air intake G4, F5, F6 F5, F6, F7, F8
Cleanrooms Pharmaceuticals, Biotech labs In ASUs for fresh air intake F5, F7
Electronics & Semiconductor In ASUs for fresh air intake F5, F7
Food & Beverages, Hospitals In ASUs for fresh air intake F5, F7
Research Labs In ASUs for fresh air intake F5, F7
Others In ASUs for fresh air intake F9
Gas Turbines Air Supply Units G4, F5
Textiles In AHUs for fresh air intake in process area F5, F7 F9
Chemical & Fertilisers In AHUs for fresh air intake in process area G3-G4 F5

Application as plenum
The product selection matrix is to highlight the potential application areas and for starting paint reference only. However, for specific application requirement, users’ ore requested to consult our product specialists.

Mini Pleat HEPA Filters

Minipleat HEPA Filters

MET Mini pleat HEPA filters are made from water resistant, fire retardant, imported micro fine glass fibre media. These filters are designed to accommodate higher airflow volumes for space saving. The filter packs are manufactured with the latest imported miniplate manufacturing machine. This category of filters is widely used for laminar flow benches, bio safety cabinets, dispensing booths and as terminal filters in cleanroom.

You could choose from the following options:

Frame: Anodised extruded aluminium, MS powder coated, 55, plastic, polystyrene housing

Construction: Box/Flange type

MERV EN 779 Eurovent 4/5
12–15 F6–F9 EU7–EU9
MERV EN 1822 Eurovent 4/5
H10–H14 EU10–EU14 A, B, C, D

TECHNICAL DATA SHEET: (TESTING AS PER EN 1822, ISO 14644)

Type Product Code Dimension Rated Air Flow (CMH) dp Initial (Pa) H13 dp Initial (Pa) H14
MT 69 MT-3369 305X305X69mm 150 140 160
MT-3669 305X610X69mm 300 140 160
MT-6669 610x610x69mm 600 140 160
MT-6769 610x762x69mm 750 140 160
MT-6969 610x915x69mm 900 140 160
MT-6269 610x1220x69mm 1200 140 160
MT-6869 610x1830x69mm 1800 140 160
MT-9969 915x915x69mm 1330 140 160
MT-9269 915x1220x69mm 1800 140 160
MT-9869 915x1830x69mm 2700 140 160
MT 90 MT-3390 305X305X90mm 150 100 120
MT-3690 305x610x90mm 300 100 120
MT-6690 610x610x90mm 600 100 120
MT-6790 610x762x90mm 750 100 120
MT-6990 610x915x90mm 900 100 120
MT-6290 610x1220x90mm 1200 100 120
MT-6890 610x1830x90mm 1800 100 120
MT-9990 915x915x90mm 1330 100 120
MT-9290 915x1220x90mm 1800 100 120
MT-9290 915x1830x90mm 2700 100 120
MT 150 MT-3315 305x305x150mm 330 220 250
MT-3615 305x610x150mm 670 220 250
MT-6615 610x610x150mm 1450 220 250
MT-6715 610x762x150mm 1830 220 250
MT-6915 610x915x150mm 2220 220 250
MT-6215 610x1220x150mm 2990 220 250

DP Final Mini pleat Filters will be 750Pa

The data provided is indicative only. For actual specification, the user is requested to call our technical specialists to ascertain the correct values. Also, the data of various types and brands are comparable only if they have been tested under the same norm.

Dust holding capacity is measured according to DIN EN 779 /ASHRAE until the rated final pressure drop is achieved. In case higher final pressures at economical operations are feasible, dust holding capacity increases correspondingly.

PRODUCT SELECTION MATRIX / APPLICATION GUIDE

Markets Application Grade
Automotive OEMs & Auto Ancillary Unit In Air Supply Units for Paint shops F7–F9
Clean Rooms Pharmaceuticals, Electronic & Semiconductor, Biotech & Research labs, Hospitals - Laminar Flow benches, Dispensing booths, Bio safety Cabinets, Terminal Filters H13–H14
Others – Nuclear power plants Terminal Filters H13, H14, U15, U16
Textiles Fresh Air Intake H11, H13
Gas Turbines Air Supply Units F6, H10

The product selection matrix is to highlight the potential application areas and for starting point reference only. However, for specific application requirement, users are requested to consult our product specialists.

Minipleat Gel Seal HEPA Filters

Minipleat Gel Seal HEPA Filters

MET Mini Pleat Gel Seal HEPA Filters are an advanced version of conventional mini pleat filters in which the gasket is replaced by silica gel, ensuring 0% leakage from the side/flanges. These are made with very high efficiency micro-fiber glass paper media, interspaced with hot melt pleating and enclosed in an aluminium extruded section.

These filters are designed to accommodate higher airflow volumes for space saving.
The filter packs are manufactured with the latest imported mini pleat manufacturing machine.
This category of filters is widely used for laminar flow benches, bio safety cabinets, dispensing booths, and as terminal filters in cleanrooms.

You could choose from the following options:

Frame: Anodised extruded aluminium

Construction: Box/Flange type

Filter Class MERV Rating Filter Euro vent Class Frame Depth Testing Standard
H13-H14 MERV-19 EU-13/EU-14 81 EN:1822
MERV-19 EU-13/EU-14 105 EN:1822
MERV-19 EU-13/EU-14 149 EN:1822

MINIPLEAT GEL SEAL HEPA FILTER TECHNICAL PARAMETERS

Filter Size CFM Efficiency IPD (Pa) FPD (Pa) Max. Pressure (Pa) Temperature (°C)
610x610x81 mm50099.99% @ 0.3 Mic250600100070
450x450x81 mm27599.99% @ 0.3 Mic250600100070
305x305x81 mm12599.99% @ 0.3 Mic250600100070
610x610x105 mm100099.99% @ 0.3 Mic250600100070
450x450x105 mm55099.99% @ 0.3 Mic250600100070
305x305x105 mm25099.99% @ 0.3 Mic250600100070
610x610x149 mm160099.99% @ 0.3 Mic250600100070
450x450x149 mm90099.99% @ 0.3 Mic250600100070
305x305x149 mm40099.99% @ 0.3 Mic250600100070
Met Air Geal Hepa Housing

Met Air Gel Hepa Housing

Met Air Geal Hepa Housing terminal boxes are manufacturing using fine material as per the set standard of the industry.  terminals are used to install gel seal mini pleat heaps filters. Each terminal boxes are equipped with perforated diffusers inside the hood for air distribution. Terminal boxes have arrangement of installing / mounting on non-walk able & walk able false ceilings/slabs & can also be hanged from the ceiling. Terminal boxes can be Top/ Bottom loading depending on the site situation & requirement.

OT PLENUM

OT PLENUM

Laminar Air Flow plenum is used to create a sterile working area free of bacterial contamination generally located above the operation table & is made of Aluminium/ SS-304 Sheet for suitable strength. In case of Aluminium after the completion of initial fabrication, the plenum is cleaned & powder Coated to give additional protection & Aesthetic look. The Laminar Air Flow is designed in such a way so as to cover the entire operation table, sterile surgical equipment’s & doctors. Each Plenum is equipped with provision of fixing of HEPA Filters, DOP port (Required for HEPA filter integrity test) & built in dampers for controlling the air flow across the HEPA Filters. Provision for fixing the lights is also given if required. Double Skinned plenum is also available.

Standard Sizes: –

2400mm X 2400mm

2400mm X 1800mm

1800mm X 1800mm

1200 mm x 1200mm

Perforated Grills:

SS-304 or Aluminum Powder Coated Perforated grills made from 16 Gauge Aluminum sheet is provided over the HEPA filter face to prevent it from physical damage.

Hepa Filters 0.3 Microns
Efficiency 99.97% Down to 0.3 Micron / 99.99% Down to 0.3 Mic
IPD 25 mm WG / 15 mm of WG
FPD 65 mm WG
Casing Aluminum Frame
Media Imported Submicronic Fiber Glasspaper Pleated with Corrugated Aluminum Separators
Euro Vent Class EU-13 / EU-14
Filter Class H-13 / H-14
MERV Rating MERV-19 / MERV-20
Temperature Ambient
Gasket Food Grade
Met Air Fan Filter Unit

Met Air Fan Filter Unit

FFU (Fan Filter Units) are used in cleanroom facilities to reduce the concentration of particles.

FFUs are typically installed in a grid pattern on the ceiling of a cleanroom to provide a continuous flow of clean and filtered air from above. This downward laminar airflow helps maintain a controlled and clean environment by preventing airborne particles from settling on surfaces or contaminating sensitive processes or products.

Applications Applications
Cleanroom Precision Optical Industry
Health and Research Institutes Operating Theatres
Composites Industry Food Processing Industry
Pharmaceutical & Laboratories Semiconductor
Parameter Details
MOC Galvanized, Stainless Steel, Galvalume, Aluminum
Power Supply 220V 50/60Hz
Air Flow Control 3 speeds / Step less control
Motor Type EC and AC
Filter Mini Pleat HEPA filter
Standard / Certificate H14 filter as per EN1822
Separator Style Hot Melt Separators
Gasket Material and Position Rubber Gasket at Air Entry Side of Filter
Noise s55dB for EC, s60dB for AC
Air Velocity 90 FPM
Power Consumption 85 Watt
Model Outer Dimension (L x W) mm Filter Dimension (L x W x H) mm Air Velocity (FPM) Total Static Pressure IPD Motor
1 610x610 600x600 90 300 150 EC/AC
2 610x915 600x900 90 300 150 EC/AC
3 610x1220 600x1200 90 300 150 EC/AC
4 1220x1220 1200x1200 90 300 150 EC/AC
Combination of Pre Filter

Combination Filters

MET series is a combination of pre filter and fine filter, fabricated and assembled in a single housing.
A separate filter mounting frame for the pre filter has been done away with.
It is available in both cassette and bag filter versions.

Standard Rating
MERV 5+9-7+15
EN 779 G3+F5-G4+F9
Eurovent 4/5 EU3+F5-EU4+F9

FRACTIONAL EFFICIENCY FOR FILTER CLASSES G1 TO F9 ACCORDING TO DIN EN779 STANDARD UNLOADED, CLEAN FILTER

Custom Color Marquee
Efficiency in%
Practical Size G1 G2 G3 G4 F5 F6 F7 F8 F9
0.1 µm - - - - 0-10 5-15 25-35 35-45 45-65
0.3 µm - - - 0-5 5-10 10-25 45-60 65-75 75-85
0.5 µm - - 0-5 5-15 15-30 20-40 60-75 80-90 90-95
1 µm - 0-15 5-15 15-35 30-50 50-65 85-95 95-98 >98
3 µm 0-5 5-15 15-35 30-55 70-90 85-95 >98 >98 >99
5 µm 5-15 15-35 35-70 60-90 90-99 95-99 >98 >98 >99
10 µm 40-50 50-70 70-85 80-98 >99 >99 >99 >99 >99

COMPOSITE AVERAGE PARTICLE SIZE EFFICIENCY % IN SIZE RANGE, µM

Range 0.30-1.0 0.30-1.0 0.30-1.0
1n/an/aE3<20
2n/an/aE3<20
3n/an/aE3<20
4n/an/aE3<20
5n/an/a20<E3<35
6n/an/a35<E3<50
7n/an/a50<E3<70
8n/an/a70<E3
9n/aE2<5085<E3
10n/a50<E2<6585<E3
11n/a65<E1<8085<E3
12n/a80<E290<E3
13E1<7590<E290<E3
1475<E1<8590<E290<E3
1575<E1<9590<E290<E3
1695<E195<E290<E3

COMPARATIVE OVERVIEW OF FILTER TEST METHODS AND FILTER CLASSIFICATION USED IN THE USA AND EUROPE